1RE 021012AC

MIDI industrial relay, 2 contacts 12V a.c.
Power supply 12V a.c.
2 changeover contacts 10A / 250V

MIDI industrial relay, 2 contacts 12V a.c.
Power supply 12V a.c.
2 changeover contacts 10A / 250V


TECHNICAL SPECIFICATIONS

Main data

Type:
MIDI-2

Power supply voltage:
12 - 24 - 48 - 60V d.c. (mod DC)
12 - 24 - 48 - 110 - 230V a.c. (mod AC)

Rated load:
10A / 250Va.c. - 30V d.c. (MIDI-2)
5A / 250Va.c. - 30V d.c. (MIDI-4)

Load in AC1:
12A / 250Va.c. - 30V d.c. (MIDI-2)
6A / 250Va.c. - 30V d.c. (MIDI-4)

Max commutable power:
2500VA / 300W (MIDI-2)
1250VA / 300W (MIDI-4)

Max commutable voltage:
250V a.c. / 30V d.c.

Motor power:
1/3 HP a 240V a.c. (MIDI-2)
1/6 HP a 240V a.c. (MIDI-4)

Contact material:
AG - CdO

Type of Operation:
monostable


Description

Use:
tertiary / industrial

Type of outputs:
potential-free changeover

Available contacts:
2 changeover (2 x ) (MIDI-2)
4 changeover (3 x ) (MIDI- 4)

Dimensions (L x W x H) mm:
21,5 x 28 x 36

Weight:
37 g.


General data

Type of installation:
on socket

Protection degree (IP):
IP 20

Electrical life (operations):
100.000

Mechanical life (operations):
10.000.000

Insulation resistance (500 V d.c.):
1.000 MO

Dielectric strength (open contacts):
750 V a.c. (MIDI-2)
1.550V a.c. (MIDI-4)

Dielectric strength (contacts/coil):
3.750 V a.c.

Minimum load:
100 mA / 5 V d.c.

Dissipated power:
0.9 W (mod DC)
1.2 VA (mod AC)

Operating temperature limits from:
-55°C to +70°C

Intervention time (with rated voltage)
25 msec max

Release time (with rated voltage):
25 msec max

Room temperature:
-55 ÷ + 70 °C

Resistance to vibrations:
10 ÷ 55 Hz 1.5 mm

Resistance to collisions (functional):
100 m / sec2 /10 g

Resistance to collisions (destructive):
1.000 m / sec2 /100 g

Humidity:
35 % ÷ 95 %

Construction:
dust-proof cover

Insulation rated voltage:
250 V

Withstand voltage at rated imp.:
2,2 KV

Pollution rating:
2

Overvoltage category:
III

Perry
Electric
Srl

Via Milanese, 11
22070 Veniano (CO)

Tel. +39 031 89441

Sales

Italy: venditalia@perry.it
Export: export@perry.it

Careers

Open Positions:
visit our page on Linkedin

Spontaneous Candidacy: candidature@perry.it

Event report Whistleblowing
https://perryelectric.wallbreakers.it/#/
Procedure Whisteblowing

Ask for information

Fulfill the form below to receive more information.