Menu driven weekly-yearly time switch 1 channel - 2 DIN
Menu driven weekly-yearly time switch 2 channels - 2 DIN
TECHNICAL SPECIFICATIONS
Power supply voltage 230V a.c. 50 - 60Hz
Contact rated data potential-free NC contact16 (2) A / 250V a.c.
Limited current NO contact zero crossing 16 (10) A / 250V a.c.
Max program number (ON-OFF) 64 (matchable in blocks of days)
ON - OFF minimum connection time 1 second
Displays 1” 1/3 backlit LCD display
Power: Incandescent LPs 3000 W
Power: Fluorescent tube LPs, not compensated 1100 W
Power: Parallely comp. fluorescent tube LPs 900W (tot capacity 125 µF)
Power: Compact, fluorescent LPs 7 W ÷ 23 W (max. 23 lamp.)
Power: LED MAX n° 25 x 4 W / 12 x 8 W / 8 x 15 W
Max cross-section of wires to terminals 6 mm2
Protection degree (IP) IP 20 - IP 40 (on rear of switchboard)
Type of output terminals with captive screw
Insulation class II
ON / OFF relay signalling ON / OFF in LCD display
Charge reserve 6 years
Type of reserve LITHIUM battery
Time tolerance + - 0.5 sec/day
Operating temperature limits 0°C / +50°C
Storing temperature -10°C / +65°C
Type of installation DIN rail / on rear of switchboard
Housing thermoplastic - grey RAL 7035
Type of use civil / tertiary / industrial
Controls multifunction keys (menu programming)
confirmation key
Clock setting accuracy digital for hours / minutes
Daylight saving time change automatic
Programming menu driven - programs protected in EEPROM
Dimensions (L x W x H) mm 35 x 60 x 90