1GA 4400CO/A

CO Sensor - IP 55 housing made in die-cast aluminium

Microprocessor probe to detect TOXIC GASES, such as carbon monoxide, with self-diagnosis. It is used when the maximum allowed 300ppm CO concentration is e

CO Sensor - IP 55 housing made in die-cast aluminium

Microprocessor probe to detect TOXIC GASES, such as carbon monoxide, with self-diagnosis. It is used when the maximum allowed 300ppm CO concentration is exceeded, or rather in case low but damaging concentrations 30ppm for 2 hours persist for long periods in the premises.


TECHNICAL SPECIFICATIONS

Power supply 12-24V d.c. +/- 10% Electrochemical cell

Catalytic sensor for LPG gas having a duration of 5 years

Detector measurement field 0÷20% LIE

Analogue output signal 4 mA ÷ 20 mA

Protection degree IP 55

Max control unit distance 100m

Probe body material: aluminium

Working temperature limit -10°C +40°C

Power supply indicator LED

Dimensions (L x W x H) 158 x 75 x 100 mm

Perry
Electric
Srl

Via Milanese, 11
22070 Veniano (CO)

Tel. +39 031 89441

Sales

Italy: venditalia@perry.it
Export: export@perry.it

Careers

Open Positions:
visit our page on Linkedin

Spontaneous Candidacy: candidature@perry.it

Event report Whistleblowing
https://perryelectric.wallbreakers.it/#/
Procedure Whisteblowing

Ask for information

Fulfill the form below to receive more information.